| 2004-11-24 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04100894 |
| | ADD: 2600 N MILITARY TRL |
| | CONT: THE WEITZ CO. |
| | TEL: (561)723-5976 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF |
| | COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING |
| | AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A |
| | THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE |
| | SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE |
| | SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | 3)WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 4) W.P.B. AMENDMENT 105.13.4.4 ALL |
| | PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO |
| | BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR |
| | ENGINEER OF RECORD CON- TAIN A |
| | STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 5) PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE |
| | REQUIRES |
| | AN ADDITIONAL 6".A-8, ELE 16.5'. |
| | |
| | 6)FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITLY KNOWN OR IS IN |
| | QUESTION |
| | THE BUILDING OFFICIAL MAY REQUIRE |
| | EXPLOR |
| | ATIONS, TEST OR OTHER ADEQUATE PROOF AS |
| | TO THE PERMISSIBLE SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | PLAANS, SPECIFICATIONS REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY A |
| | PROFESSIONAL ENGINEER AND BEING FILED |
| | FOR PUBLIC RECORD SHALL HAVE THE |
| | SIGNATURE AND THE SEAL OF THE DESIGN |
| | PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ST S 61G15-23.002 ENGINEERS |
| | |
| | 7) SHEET S-5.3 CODES & STANDARDS 1-A, |
| | TABLE 1606 IMPORTANCE FACTOR, BUILDINGS |
| | OR STRUCTURES WITH OCCUPANT LOADS |
| | GREATER THAN 300 IN A SINGLE ROOOM, THE |
| | IMPORTANCE FACTOR SHALL BE 1.15, |
| | BUILDING CATEGORY III. |
| | |
| | 8) SP-2 THE HANDICAPPED ENTRANCE VS THE |
| | |
| | MAIN ENTRANCE, THE ACCISSIBLE ROUTE |
| | SHOULD BE THE SAME ROUTE TO THE MAXIMUM |
| | EXTENT USED BY THE GENERAL PUBLIC, SEE |
| | 11-4.3.2(1). |
| | |
| | 9) SHEET A1.1/A6.1 RETRACTABLE BENCHES, |
| | THEY DO SHOW COMPANION SEATING BUT NO |
| | INFORMATION AS TO HOW TO COMPLY WITH |
| | VERTICAL ACCESSIBILITY. 11-4.1.2 |
| | VERTICAL ACCESSIBILITY, NOTHING IN THIS |
| | CODE SHALL BE CONSTRUED TO RELIEVE THE |
| | OWNER OF ANY BUILDING, SSTRUCTURE OR |
| | FACILITY FROM THE DUTY TO PROVIDE |
| | VERTICAL ACCESSIBILITY TO ALL LEVELS |
| | ABOVE OR BELOW THE OCCUPIAABLE GRADE |
| | LEVEL. IF NOT SUPPLYING A LIFT AND |
| | COMPANION SEATING TO ALL LEVELS, APPLY |
| | TO THE STATE FOR A WAIVER. |
| | |
| | 10) SHEET A2.1 DOORS 127, 128& 129 THE |
| | DOOR SCHEDULE INDICATES A FRAME TYPE"6" |
| | FOR A 6'-0" WIDE SET OF DOORS, WHERE |
| | ITSHOULD READ A 3'-0" DOOR WITH SIDE |
| | LIGHT. THE SCHEDULE INDICATES THE 3'-0" |
| | |
| | FRAME WITH SIDELIGHT THERE IS ONLY 16" |
| | ON THE LATCH SIDE OF THE DOORWAY WHERE |
| | 18" IS REQUIRED, SEE 11-4.13.6. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING |
| | CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 11) SHEET A2.1/ A2.2 DOORS IN SERIES |
| | SEE |
| | 11-4.13.7. DOORS 164A&B, 159A&B, 154A&B |
| | AND DOOR 151A&B. |
| | |
| | 12) SEE A2.1/ A2.2 VARIOUS STORAGE ROOM |
| | & MECHANICAL ROOM DOORS SWING OUT INTO |
| | THE COORIDOR, SEE 1021.4 DOORS THAT |
| | SWING INTO AN EXIT ACCESS COORIDOR |
| | SHALL |
| | BE RECESSED TO PREVENT INTERFERENCE |
| | WITH CORRIDOR TRAFFIC; ANY DOORS NOT |
| | RECESSED SHALL OPEN 180 DEGREES TO STOP |
| | AGAINST THE WALL. |
| | |
| | 13) A2.2 ROOM 141/142 THERE IS A LINE |
| | DOWN THE CENTER OF THIS ROOM BUT NO |
| | INFORMATION AS TO TYPE OF WALL. THIS |
| | ROOM TO BE USED AS A WEIGHT/ FITNESS |
| | ROOM WITH NO EQUIPMENT SHOWN ON PLANS |
| | WILL HAVE A OCC LOAD OF 136 OCC LOAD. |
| | THIS WILL REQUIRE 2 EXITS 1/2 THE |
| | DIAGONAL APART UNSPRINKLERED, 1/3RD |
| | THE DIAGONAL(MINIMAL) FOR SPRINKLERED |
| | BLDGS. |
| | |
| | 14) A2.1 CLASSROOM 123 VS OFFICE |
| | 115/116 |
| | SINCE THERE IS A MIXED OCCUPANCY, TABLE |
| | |
| | 704.1 INDICATES A 2HR WALL BE BETWEEN |
| | THESE OCCUPANCIES. |
| | |
| | 15) A2.1 CORRIDORS 130, 122, 165 & 148 |
| | ALL INDICATE THE USE OF A TYPE (3) WALL |
| | SYSTEM, THIS UL- U404 INDICATES A 1HR |
| | AND A 2HR WALL. THE DETAIL ONLY |
| | PROVIDES |
| | |
| | THE INFORMATION FOR THE 1 HR WALL. |
| | PROVIDE THE INFORMATION FOR A 2 HR |
| | RATING? |
| | |
| | 16) A2.1 ADDITIONAL INFO REQUIRED, |
| | NO RATING FOR THE WALL BETWEEN THE |
| | ENTRY |
| | 126AND THE STUDENT LOUNGE? |
| | |
| | 17) THE SAME WALL LISTED ABOVE, PROVIDE |
| | THE SEAL TO THE ROOF DECK ABOVE: |
| | 705.7.1 JOINTS INSTALLED IN OR BE- |
| | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- |
| | TANT FLOORS OR FLOOR/ CEILING |
| | ASSEMBLIES |
| | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- |
| | ING ASSEMBLIES SHALL BE PROTECTED BY AN |
| | APPROVED FIRE RESISTANT JOINT SYSTEM |
| | DESIGNED TO RESIST THE PASSAGE OF FIRE |
| | FOR A PERIOD NOT LESS THAN THE RE- |
| | QUIRED FIRE RESISTANCE RATING OF THE |
| | WALL, FLOOR OR FLOOR IN OR BETWEEN |
| | WHICH IT IS INSTALLED. |
| | |
| | |
| | 18) 704.2.1.4 CORRIDOR PARTITIONS, |
| | SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO |
| | THE |
| | AUTHORITY HAVING JURISDICTION. SUCH |
| | IDEN |
| | TIFICATION SHALL BE ABOVE ANY |
| | DECORATIVE |
| | CEILING CEILING AND IN CONCEALED |
| | SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 19) A3.1 DOOR SCHEDULE, THE DOOR |
| | SCHEDULE INDICATES THE USE OF "B" LABEL |
| | DOORS, SEE TABLE 705.1.2 OPENING |
| | PROTECTIVES ARE LABELED IN MINUTES AND |
| | HRS. |
| | |
| | 20) 8A.3 DETAILS 1&4, THESE DETAILS DO |
| | NOT INDICATE HOW THE WINDOW WALL IS TO |
| | BE ATTACHED TO THE HORIZONTAL STEEL |
| | FRAMING MEMBER. |
| | |
| | 21) A8.3 DETAIL 3 DOES INDICATE THERE |
| | SHALL BE FASTENERS BUT WHAT TYPE OF |
| | FASTENER AND SPACING. |
| | |
| | 22) A8.3 DETAIL 2 INDICATES THE USE OF |
| | " BUTT GLAZING" SEE SECTION FBC 2406.2. |
| | |
| | 23) A8.3 DETAIL (1) IS MISSING |
| | INFORMATION ON HOW THE STUCCO FRIEZE |
| | ABOVE THE GLASS WALL (LOBBY) IS TO BE |
| | BUILT, NO INFORMATION IS FOUND ON THE |
| | STRUCTURAL SHEETS. |
| | |
| | 24) A8.3 DETAIL 4 NEEDS ADDITIONAL |
| | INFORMATION, MISSING WIRE LATH WEIGHT, |
| | "C" CHANNEL SPACING AND STEEL CEILING |
| | JOIST (METAL STUDS) WEIGHT AND SIZE. |
| | |
| | 25) A7.5 INDICATES THE TERM "METAL STUDS |
| | AS NECESSARY TO SUPPORT DRYWALL |
| | CEILING", PLEASE PROVIDE THE ALLOWABLE |
| | CEILING SPAN DEFLECTION, PSF, IF MIDSPAN |
| | IS TO BE SUPPORTED, SIZE OF STUD AND |
| | THICKNESS AND JOIST SPACING. |
| | |
| | THIS REVIEW WILL CONTINUE UNDER A |
| | SECOND |
| | BUILDING SESSION. |
| | |
| | SPACING |
| | GLAZING" |