| Plan Review Notes For Permit 04100855 |
| Permit Number |
04100855 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-16 00:00:00 | DENIED: | | | 1.PLAN SHEET M101, PLAN INDICATES | | | BATHROOM EXHAUST "EXISTING FLEX".PER | | | 2001 FBC(M) 501.5, EXHAUST DUCTS SHALL | | | BE OF METAL. | | | | | | 2.PLAN ALSO INDICATES RETURN AIR FROM | | | THE BATHROOM AREAS, AIR SHALL NOT BE | | | RECIRCULATED PER 2001 FBC(M) 403.3 & | | | 501.2. | | | | | | 3.PLAN SHEET A100 INDICATES TREATMENT | | | RM #7 AS A "CLOSED SYSTEM", PLEASE | | | CLARIFY WHAT IS MEANT BY A "CLOSED | | | SYSTEM".WHAT TYPE OF "TREATMENT" WILL | | | BE CONDUCTED? | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. | | | |
|