2004-11-16 00:00:00DENIED:
 1.PLAN SHEET M101, PLAN INDICATES
 BATHROOM EXHAUST "EXISTING FLEX".PER
 2001 FBC(M) 501.5, EXHAUST DUCTS SHALL
 BE OF METAL.
  
 2.PLAN ALSO INDICATES RETURN AIR FROM
 THE BATHROOM AREAS, AIR SHALL NOT BE
 RECIRCULATED PER 2001 FBC(M) 403.3 &
 501.2.
  
 3.PLAN SHEET A100 INDICATES TREATMENT
 RM #7 AS A "CLOSED SYSTEM", PLEASE
 CLARIFY WHAT IS MEANT BY A "CLOSED
 SYSTEM".WHAT TYPE OF "TREATMENT" WILL
 BE CONDUCTED?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719.
  