| Date |
Text |
| 2004-10-26 00:00:00 | *************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE PROVIDE ALL INFORMATION |
| | ON TITLE BLOCK AS REQUIRED UDNER FAC |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE SEE MISSING FIRM LICENSE #. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 2)NOTE: PLEASE SEE RISER AND PANEL SCHED |
| | -ULE BOTH INDICATE 200A PANEL AS NEW. |
| | PLEASE SEE PLAN LAYOUT SHOWS PANEL AS |
| | EXISTING?? PLEASE CORRELATE. |
| | |
| | 3)NOTE: PLEASE SEE EXT/ EM LTS APPEAR |
| | TO BE SHOWN AS BEING SWITCHED?? |
| | THESE ARE NOT PERMITTED TO BE SWITCHED |
| | AND MAY JUST NEED A NOTE TO MENTION: |
| | "TO BE WIRED AHEAD OF ANY LOCAL SWITCH" |
| | ?? |
| | |
| | 4)NOTE: PLEASE ALSO PROVIDE AIC RATING |
| | FOR NEW MCB SHOWN BELOW METER. |
| | AIC RATING OF NEW PANEL IS NOTED: |
| | 110.9,215.5 |
| | |
| | 5)NOTE: PLEASE PROVIDE LOAD ON EXISTING |
| | 800A WIREWAY. |
| | 215..5,220 |
| | |
| | 6)NOTE: PLEASE SEE 220.13 FOR MIN 180VA |
| | PER RECEPT/YOKE. PLEASE SEE LOADS ON |
| | PANEL SCHEDULE DO NOT SEEM TO CORRELATE |
| | WITH THE # OF RECEPTS ON SOME RECEPT |
| | CIRCUITS. |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AN |
| | INSERT NEW INTO TWO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | |
| | ***PLEASE NOTE: THIS IS ONLY IN FOR PLAN |
| | REVIEW AT THIS TIME AND NOT FOR PERMIT. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |