Plan Review Notes
Plan Review Notes For Permit 04100855
Permit Number 04100855
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-26 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE PROVIDE ALL INFORMATION
 ON TITLE BLOCK AS REQUIRED UDNER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE MISSING FIRM LICENSE #.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE RISER AND PANEL SCHED
 -ULE BOTH INDICATE 200A PANEL AS NEW.
 PLEASE SEE PLAN LAYOUT SHOWS PANEL AS
 EXISTING?? PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE EXT/ EM LTS APPEAR
 TO BE SHOWN AS BEING SWITCHED??
 THESE ARE NOT PERMITTED TO BE SWITCHED
 AND MAY JUST NEED A NOTE TO MENTION:
 "TO BE WIRED AHEAD OF ANY LOCAL SWITCH"
 ??
  
 4)NOTE: PLEASE ALSO PROVIDE AIC RATING
 FOR NEW MCB SHOWN BELOW METER.
 AIC RATING OF NEW PANEL IS NOTED:
 110.9,215.5
  
 5)NOTE: PLEASE PROVIDE LOAD ON EXISTING
 800A WIREWAY.
 215..5,220
  
 6)NOTE: PLEASE SEE 220.13 FOR MIN 180VA
 PER RECEPT/YOKE. PLEASE SEE LOADS ON
 PANEL SCHEDULE DO NOT SEEM TO CORRELATE
 WITH THE # OF RECEPTS ON SOME RECEPT
 CIRCUITS.
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AN
 INSERT NEW INTO TWO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 ***PLEASE NOTE: THIS IS ONLY IN FOR PLAN
 REVIEW AT THIS TIME AND NOT FOR PERMIT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  