Plan Review Notes
Plan Review Notes For Permit 04100842
Permit Number 04100842
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-25 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE.
  
 2)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT. 600.5 IS THIS A TENANT
 SPACE?
  
 3)NOTE: PLEASE SEE POSSIBLE FIRE REVIEW
 COMMENTS FOR ANY EM/EXT LTS AND SEE
 700.12E FOR CIRCUITING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]