| Plan Review Notes For Permit 04100830 |
| Permit Number |
04100830 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) FROM PREVIOUS REVIEW: | | | SUBMIT A DETAIL FOR DRINKING FOUNTAIN | | | SHOWING COMPLIANCE WITH SECTION 11-4.15 | | | AND ALL SUBSECTIONS. | | | 2) FROM PREVIOUS REVIEW: | | | IF PRACTICING THROUGH A DULY AUTHORIZED | | | ENGINEERING BUSINESS, ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME AND LICENSE | | | NUMBER, AS WELL AS THE NAME, ADDRESS, | | | AND CERTIFICATE OF AUTHROIZATION NUMBER | | | OF THE ENGINEERING BUSINESS ON EACH | | | SHEET. FAC 61G15-23.002(2) & FS | | | 471.025. | | | *********NEW COMMENTS********* | | | 1B) REMOVE ALL VOIDED SHEETS AND SUBMIT | | | ONE SET OF VOIDED SHEETS FOR COMPAIRSON. | | | SUBMIT TWO SETS OF PLANS FOR REVIEW. | | | SECTION 104.2.1. | | | 2B) SEE ATTACHED SHEET CONCERNING DESIGN | | | PROFESSIONAL AND FS 553.80(2)(B). | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|