| 2004-10-25 00:00:00 | *************** UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE INCLUDE ALL LICENSE #'S |
| | ON TITLE BLOCK AS REQUIRED UNDER FAC |
| | 61G15-23.002, FS 471.023. |
| | |
| | 2)NOTE: PLEASE SEE PANEL SCHEDULE INDI- |
| | -CATES NEW AND EXISTING SIGN CIRCUIT, |
| | HOWEVER THIS COULD NOT BE LOCATED ON |
| | PLANS AT LOCATION REQUIRED PER 600.5 |
| | |
| | 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE ALSO SHOW LOADING/CALCS FOR TRK |
| | LTS PER 220.12 |
| | |
| | 4)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULES. PLEASE SEE 700.12E |
| | FOR CIRCUITING OF EM/EXT LTS. |
| | |
| | 5)NOTE: PLEASE SEE RISER DIAGRAM |
| | MENTIONS TO VERIFY A MIN OF 100A SERVICE |
| | TO EACH PANEL. |
| | THIS NEEDS TO BE VERIFIED AT THIS TIME |
| | AND PLACE ON PLANS FOR CODE COMPLIANCE |
| | AND MEETING MIN LOADS. |
| | 215.5 |
| | |
| | PLEASE SEE POSSIBLE COMMENT FROM OTHER |
| | REVIEWER(S) AS THEY MAY HAVE AN AFFECT |
| | ON ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND INSERT ONLY NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |