2006-04-05 00:00:00REVISION CHECKLIST:
  
 1- DRAWING A1 OF 7: IDENTIFY MULLION
 SIZE ABOVE 12' WIDE SLIDING GLASS DOORS
 IN FAMILY ROOM. SEC. 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 REVISED DRAWING A1 ONLY CALLS FOR
 STRUCTURAL MULLION AND ANCHORS TO BE
 ATTACHED WITH.
 (NOTE: ENGINEER'S DETAIL FOR 16' WIDE
 SLIDING GLASS DOORS IS OK).
  
 2- DADE COUNTY NOA #03-0225.07 FOR
 ALUMINUM TUBE MULLIONS W/STEEL
 REINFORCEMENTS PRODUCT APPROVAL
 SUBMITTED DOESN'T WORK FOR 12'X8'
 SLIDING GLASS DOORS AND TRANSOM ABOVE IN
 FAMILY ROOM. MAXIMUMWINDOW WITDH
 SHOWING IN TABLES IS 75". NEED 90" WIDTH
 FOR PROPOSED INSTALLATION.
  
 2- THE FOLLOWING WAS REQUESTED ON
 CHECKLIST DATED 2-06-06 AND WAS NOT
 PROVIDED:
 SHEET A3 OF 7: PROVIDE CALCULATIONS TO
 SHOW WHY ONLY 1 SCREW PER ROOF TILE IS
 ENOUGH TO RESIST THE UPLIFT. SECTION
 1606.3.3 FBC 2001 AND SECTIONS 104.2.1.2
 AND 104.2.1.1 CITY AMENDMENTS TO FBC
 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  