| Plan Review Notes For Permit 04100804 |
| Permit Number |
04100804 |
|
| Review Stop |
B |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2006-04-05 00:00:00 | REVISION CHECKLIST: | | | | | | 1- DRAWING A1 OF 7: IDENTIFY MULLION | | | SIZE ABOVE 12' WIDE SLIDING GLASS DOORS | | | IN FAMILY ROOM. SEC. 104.2.1.2 OF CITY | | | AMENDMENTS TO FBC 2001. | | | REVISED DRAWING A1 ONLY CALLS FOR | | | STRUCTURAL MULLION AND ANCHORS TO BE | | | ATTACHED WITH. | | | (NOTE: ENGINEER'S DETAIL FOR 16' WIDE | | | SLIDING GLASS DOORS IS OK). | | | | | | 2- DADE COUNTY NOA #03-0225.07 FOR | | | ALUMINUM TUBE MULLIONS W/STEEL | | | REINFORCEMENTS PRODUCT APPROVAL | | | SUBMITTED DOESN'T WORK FOR 12'X8' | | | SLIDING GLASS DOORS AND TRANSOM ABOVE IN | | | FAMILY ROOM. MAXIMUMWINDOW WITDH | | | SHOWING IN TABLES IS 75". NEED 90" WIDTH | | | FOR PROPOSED INSTALLATION. | | | | | | 2- THE FOLLOWING WAS REQUESTED ON | | | CHECKLIST DATED 2-06-06 AND WAS NOT | | | PROVIDED: | | | SHEET A3 OF 7: PROVIDE CALCULATIONS TO | | | SHOW WHY ONLY 1 SCREW PER ROOF TILE IS | | | ENOUGH TO RESIST THE UPLIFT. SECTION | | | 1606.3.3 FBC 2001 AND SECTIONS 104.2.1.2 | | | AND 104.2.1.1 CITY AMENDMENTS TO FBC | | | 2001. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | |
|