| Plan Review Notes For Permit 04100804 |
| Permit Number |
04100804 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2006-02-06 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- A/C AREA WAS CHANGED AGAIN. NEED TO | | | REVISE THE ENERGY CALCULATIONS TO MATCH | | | A/C AREA SHOWN ON REVISED PLANS. | | | | | | 2- ARCHITECT TO SPECIFY MULLION SIZE AND | | | ANCHORS FOR STRUCTURAL MULLION ABOVE | | | SLIDING GLASS DOORS. SPECIFICATIONS | | | SHOWN ON SHEET A1 OF 7 ONLY SPECIFIES | | | THE TAPCONS. IT DOESN'T SPECIFY MULLION | | | SIZE. | | | NOTE: 2"X HEAVY WALL-ALUMINUM MULLION | | | DOESN'T RESIST THE DESIGN PRESSURES FOR | | | SLIDING GLASS DOOR AT LIVING ROOM. SEE | | | PRODUCT APPROVAL. | | | | | | 3- PROVIDE FLORIDA OR LOCAL PRODUCT | | | APPROVAL FOR SPECIFIED STRUCTURAL | | | MULLION BETWEEN SLIDING GLASS DOORS AND | | | TRANSOMS ABOVE. SEE ARCHITECT'S RESPONSE | | | TO ITEM #2 ABOVE. 2"X HEAVY | | | WALL-ALUMINUM MULLION SUBMITTED DOESN'T | | | WORK. | | | | | | 4- SHEET A3 OF 7: PROVIDE CALCULATIONS | | | TO SHOW WHY ONLY 1 SCREW PER ROOF TILE | | | IS ENOUGH TO RESIST THE UPLIFT. SEC. | | | 1606.3.3 FBC 2001 AND SEC. 104.2.1 AND | | | 104.2.1.1 CITY AMENDMENTS TO FBC 2001. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|