| Plan Review Notes For Permit 04100804 |
| Permit Number |
04100804 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-12-14 00:00:00 | BUILDING REVIEW PROVISO: | | | PROVIDE FOLLOWING INFORMATION PRIOR TO | | | CONSTRUCTION/INSTALLATION TO AVOID | | | DELAYS OR CONFLICTS AT INSPECTIONS: | | | | | | 1-REVISE DETAILS CI AND C2 ON SHEET A6 | | | TO MATCH CONDITIONS SHOWN ON ROOF | | | FRAMING PLAN. TAKE INTO CONSIDERATION: | | | A) TRUSS BEARING ELEVATION. | | | B) 2-2X12 BEAM. | | | | | | **ALSO, SPECIFY HOW ARE 2X12'S INSTALLED | | | ON MASONRY WALL. SEC. 104.2.1.2 CITY | | | AMENDMENTS TO FBC 2001. | | | | | | 2-PROVIDE FLORIDA/LOCAL PRODUCT APPROVAL | | | FOR TYPE OF ENTRY DOORS AS SHOWN ON | | | PLANS. |
|