2004-11-24 00:00:00CHECKLIST:
 1-SHEET A3: A) REVISE ROOF LOAD TABLE
 TO
 INCLUDE THE 10PSF OR 30PSF ATTIC LIVE
 LOAD AS REQ'D BY TABLE 1604.1 FBC 2001.
 B) REVISE DETAIL SECTIONS TO MATCH
 CORRECT DETAIL AND PAGE AS SHOWN ON
 PAGE
 A-6.
 C) REVISE ZONE 3 TO INCLUDE ALL
 CORNERS,
 SEE FIGURE 1606.2(C) FBC 2001.
  
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3-OWNER/AGENT TO SIGN AND DATE ENERGY
 CALCULATIONS AS REQUIRED BY SECTION
 103.3 OF CHAPTER 13 FBC 2001.
  
 4-REVISE DETAIL C/7 ON SHEET A6 TO
 MATCH
 ACTUAL CONDITIONS AS SHOWN ON ROOF
 FRAMING PLAN. SPECIFY ALL FASTENERS
 INCLUDING STUDS FASTENING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 5-NEED FLORIDA/LOCAL PRODUCT APPROVAL
 FOR: A) FIXED WINDOWS FOR LARGE MISSILE
 IMPACT, NOT FOR SMALL MISSILE IMPACT.
 B) ENTRY DOORS WITH MISSILE IMPACT
 PROTECTION AS SPECIFIED ON PLANS.
  
 6-OWES $1871.56 FOR UPDATE VALUATION AND
 BALANCE OWED AT TIME OF APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.