| 2005-02-15 00:00:00 | ******** UNSAT 2ND REVIEW ********* | | | | | | PLEASE SEE SOME NOTES FROM FIRST REVIEW | | | STILL NEED TO BE ADDRESSED. | | | | | | 1)NOTE: NOTE #1, OK, TITLE BLOCK FOR | | | JOHN AVERCAMP REMOVED. | | | | | | 2)NOTE: NOTE #2 NO. | | | SUBMIT AIC RATING S FOR MAINS/ SERVICE | | | PER 110.9/215.5 | | | | | | 3)NOTE: NOTE #3 OK. | | | NOTED ON PLANS. | | | | | | 4)NOTE: NOTE #4 NO, PLEASE SEE BOTH | | | BATHS AND GEN LTS FOR BATHS ARE SHOWN ON | | | SAME CIRCUIT. | | | PLEASE SEE 210.52D,210.11C3 | | | | | | 5)NOTE: NOTE #5, OK. | | | MOVED SD'S. | | | | | | 6)NOTE: NOTE #6 NO, PLEASE SEE | | | IRRIGATION PUMP STILL SHOWS 30A OCP ON | | | #12 AWG. | | | PLEASE SEE OTHER ITEMS WERE REVISED. | | | | | | 7)NOTE: NOTE #7 #8 AND #9 OK. | | | | | | 8)NOTE: NOTE#10 NO. NOTE ADDED FOR ARC | | | FAULT PROTECTION, HOWEVER PLEASE SEE | | | NOTE # 6 ON ELECTRICAL NOTES. | | | | | | 11)NOTE: NOTE #11, YES/NO, PLEASE SEE | | | DISC WERE ADDED HOWEVER, MANUFACTURE | | | SPECS NOT SUBMITTED. | | | PLEASE SUBMIT SPECS SHOWING LISTING FROM | | | A NRTL. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS FOR | | | REVIEW AND STAMPING. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|