| Plan Review Notes For Permit 04100753 |
| Permit Number |
04100753 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT 5 SANITARY RISER DIAGRAM DOES NOT | | | MEET THE CODE REQUIREMENTS, NOR DOES IF | | | RELEECT THE FLOOR PLAN. SECTION | | | 104.2.1. | | | A) KITCHEN SINK IS NOT VENTED. SECTION | | | 902.1. | | | B) WASH MACHINE IS NOT VENTED, REQUIRES | | | A STADPIPE, AND THE CLEANOUT SHALL BE | | | INSTALLED 4 FT. ABOVE THE FLOOR FOR | | | ACCESS. SECTIONS 902.1, 1002.1, & | | | 708.10 | | | C) MASTER BATH SHOWS 2 SHOWERE ON THE | | | SANT. RISER DIAGRAM, BUT ONLY ONE ON THE | | | FLOOR PLAN. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | D) BATH #2 IS SHOWN AS CONNECTING TO | | | THE BLDG DRAIN DOWNSTREAM OF THE | | | KITCHEN, WASH MACHINE, AND MASTER BATH | | | ON THE RISER DIATRAM, BUT UPSTREAM OF | | | THESE FIXTURES ON THE FLOOR PLAN. PLEASE | | | SHOW THE RISER AS IT WILL BE INSTALLED. | | | SECTION 104.2.1. | | | | | | 2) SEE ATTACHED SHEET SHOWING AN EXAMPLE | | | OF A SANITARY RISER DIAGRAM THAT MEETS | | | THE CODE REQUIREMENTS AND REFLECT THE | | | FLOOR PLAN. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|