| 2004-11-12 00:00:00 | ******** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS CONTAINING |
| | TITLE BLOCKS, ARE REQUIRED TO BE SIGNED, |
| | DATED AND SEALED BY PERSON RESPONSIBLE |
| | FOR PLANS. |
| | FS 481.221, 471.025 |
| | PLEASE ALSO SEE FAC 61G15-23.002, |
| | 61G1-16.004 FOR MISSING LICENSE #'S AS |
| | REQUIRED UNDER FS 481.219 AND 471.023 |
| | FOR FIRMS ETC. |
| | THIS IS REQUIRED ON ALL SHEETS WHEATHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWERS. |
| | FBC 104.2.1 |
| | |
| | |
| | 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | |
| | 3)NOTE: PLEASE SHOW ALL RECEPTS |
| | SERVING KITCHEN COUNTERSPACE AS GFI/GFI |
| | PROTECTED PER 210.8A-6 |
| | |
| | |
| | 4) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 5)NOTE: PLEASE SEE NFPA -72 8-1.4.2 FOR |
| | LOCATIONS OF SD'S. A MIN OF 3' FROM BATH |
| | DRS. |
| | |
| | 6)NOTE: PLEASE CORRELATE LOADS/OCP AND |
| | AWG ON PANEL SCHEDULE. |
| | PLEASE SEE INSTA-HOTS UNITS, SHOWS |
| | 2P30A |
| | WITH 11.8KW LOAD? |
| | PLEASE ALSO SEE LOADS SHOWN FOR COND |
| | UNIST AS 10KW, THIS SHOULD BE FOR AHU'S |
| | HOWEVER THESE ARE NOT LISTED. |
| | PLEASE ALSO SEE 424.3B FOR OCP ETC. |
| | 310.16, 240.4 |
| | |
| | 7)NOTE: PLEASE SEE 210.52E FOR MISSING |
| | FRONT AND REAR RECEPTS. |
| | |
| | 8)NOTE: PLEASE SEE 210.8 FOR ALL RECEPTS |
| | TO BE GFI/ GFI PROTECTED. |
| | |
| | 9)NOTE: PLEASE SEE 250.6,250.24, AN |
| | EQUIPMENT GRND IS NOT INSTALLEDFROM |
| | METER TO FIRST MEANS OF DISC. |
| | |
| | 10)NOTE: PLEASE SEE 2002 NEC 210.12, |
| | PLEASE LIST ARC FAULT PROETCTION ON |
| | PANEL SCHEDULE. |
| | NOTES MENTIONS SD' TO BE WIRED INTO |
| | KITCHEN/BATH LTS? THIS WOULD REQUIRED |
| | THESE TO ALSO BE ARC FAULT PROTECTED. |
| | |
| | 11)NOTE: PLEASE SHOW DISCONNECTING MEANS |
| | FOR INSTA-HOT UNITS. IF OCP, THEN THESE |
| | MUST MEET 110.26. |
| | PLEASE ALSO SEE MANUFACTS SPECS FOR |
| | CLEARENCE REQ',MENTS FOR UNITS. |
| | |
| | PLEASE SEE ONE SET OF ELECTRICAL PLANS |
| | HAVE BEEN REDLINED FOR MOST OF THE ABOVE |
| | ITEMS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD MAY BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | NOTES MENTIONS SD'S TO BE WIRED TO |
| | |
| | 7 |