| 2004-11-29 00:00:00 | CHECKLIST: |
| | 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING BACKSTAMPED DRAWINGS AND PAID |
| | RECEIPT. |
| | |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 3-RIGHT ELEVATION DON'T MATCH PLANS. |
| | THERE IS AN ADDITIONAL WINDOW SHOWN ON |
| | THE ELEVATION. REVISE AS REQUIRED. |
| | |
| | 4-SPECIFY CONCRETE SLAB JOINTS OR |
| | SPECIFY WWM SUPPORTS & SPACING AS REQ'D |
| | BY SEC. 1909.3 FBC 2001. |
| | |
| | 5-LINTEL SHEDULE DON'T MATCH SIZES. SEE |
| | FOUNDATION PLANS AND LINTEL SCHEDULE |
| | AND |
| | REVISE AS REQUIRED. |
| | |
| | 6-SPECIFY BEAM AT NOOK AREA. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 7-TYPICAL WALL SECTION: A) SPECIFY |
| | FIREBLOCKING AS REQUIRED BY SECTION |
| | 705.3.1.1 FBC 2001. |
| | B) INDICATE MIN. FOOTING EMBEDMENT AS |
| | REQUIRED BY SEC. 1804.1.3 FBC 2001. |
| | |
| | 8-REVISE PORCH DETAIL TO MATCH PORCH |
| | CONSTRUCTION SHOWN ON PLANS. PORCH |
| | SHOWN |
| | IS FOR WOOD FRAMED STRUCTURE. |
| | |
| | 9-SOIL TEST REPORT. REVISE SQUARE FOOT |
| | OF PROPOSED STRUCTURE. SEE PLANS. |
| | |
| | 10-PROVIDE 2X STRUCTURAL BUCK DETAIL |
| | FOR |
| | SWING DOORS AS REQUIRED ON THE PRODUCT |
| | APPROVAL. |
| | |
| | 11-PROVIDE FLORIDA/LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) ENTRY DOORS WITH DRAWINGS THAT MATCH |
| | THOSE SUBMITTED FOR FLORIDA BUILDING |
| | COMMISION REVIEW AND APPROVAL. |
| | B) DOOR W/ SIDELITES AS SHOWN ON PLANS. |
| | C) 45 DEGREES FIXED WINDOW SYSTEM. |
| | D) GARAGE SIDE DOOR. |
| | |
| | 12-PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS INCLUDING:A) KEY PLAN |
| | AND |
| | COMPLETE INSTALLATION SCHEDULE (SEE |
| | ATTACHED SAMPLE) |
| | B)INDICATE ON DWGS SPECIFIC MOUNTING |
| | CONDITIONS AND ANCHOR TYPE AND SPACING |
| | TO BE USED ACCORDING TO THE DESIGN |
| | PRESSURES, EDGE DISTANCE, CONNECTION |
| | TYPE, PANEL SPAN AND STRUCTURE TO BE |
| | ATTACHED TO (MASONRY OR CONCRETE). |
| | |
| | 13-SHEET 1/10: UPDATE INFORMATION. SEE |
| | COMMENTS ON PLANS. |
| | |
| | 14-SPECIFY SIZE OF WINDOW TO BE |
| | INSTALLED AT NOOK AREA. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 15-UPDATE TRUSS ANCHOR SCHEDULE. SEE |
| | LATEST CATALOGUE. OR, PROVIDE COMPLETE |
| | ENGINEERING FOR TYPE AND NUMBER OF |
| | FASTENERS THAT DIFFER FROM APPROVED AND |
| | PUBLISHED ON MANUFATURER'S CATALOGUE. |
| | SEE COMMENTS ON PLANS. |
| | **CLARIFY WHY ARE THERE ADDITIONAL |
| | FASTENERS SHOWN ON RIGHT HAND SIDE |
| | COLUMN? |
| | |
| | 16-WHICH ARE THE CONNECTORS A3 AND A4. |
| | THEY ARE NOT SHOWN ON TRUSS ANCHOR |
| | SCHEDULE. |
| | |
| | 17-ROOF FRAMING PLAN AND PORCH DETAIL |
| | TO |
| | MATCH. THEY SPECIFY DIFFERENT NUMBER OF |
| | 2X12'S. REVISE AS REQUIRED. SEE |
| | COMMENTS |
| | ON PLAN. |
| | |
| | 18-OWES $203.82 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | |
| | 19-OWNER/AGENT TO SIGN AND DATE ENERGY |
| | CALCULATIONS AS REQUIRED BY SEC. 103.1.2 |
| | CHAPTER 13 FBC 2001. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 805-6712. |