 PRIOR TO CALLING A ROUGH ELECTRICAL
 INSPECTION SUBMIT A REVISED SET OF
 PLANS SHOWING CODE COMPLIANCE WITH THE
 FOLLOWING.
  
 1} COUNTERTOP RECEPTACLE SPACING PER
 ARTICLE 210.52(C).
  
 2} REQUIRED MINIMUM OF TWO BRANCH
 CIRCUITS PER 210.11(C)(1).
  
 3} ALL RECEPTACLES SERVING THE
 COUNTERTOP MUST BE GFI PROTECTED PER
 210.8(A)(6). PLEASE INDICATE SAME ON
 PLANS.
  
 4} PLEASE SHOW PLACEMENT OF THE REQUIRED
 EGRESS LIGHTING PER 210.70.
  
 RESUBMIT THESE REVISIONS AT LEAST ONE
 WEEK PRIOR TO CALLING THE ROUGH
 INSPECTION TO INSURE THE REVIEW PROCESS
 WILL NOT HOLD UP WORK.
  