| Plan Review Notes For Permit 04100751 |
| Permit Number |
04100751 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-25 00:00:00 | | | | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PRIOR TO CALLING A ROUGH ELECTRICAL | | | INSPECTION SUBMIT A REVISED SET OF | | | PLANS SHOWING CODE COMPLIANCE WITH THE | | | FOLLOWING. | | | | | | 1} COUNTERTOP RECEPTACLE SPACING PER | | | ARTICLE 210.52(C). | | | | | | 2} REQUIRED MINIMUM OF TWO BRANCH | | | CIRCUITS PER 210.11(C)(1). | | | | | | 3} ALL RECEPTACLES SERVING THE | | | COUNTERTOP MUST BE GFI PROTECTED PER | | | 210.8(A)(6). PLEASE INDICATE SAME ON | | | PLANS. | | | | | | 4} PLEASE SHOW PLACEMENT OF THE REQUIRED | | | EGRESS LIGHTING PER 210.70. | | | | | | RESUBMIT THESE REVISIONS AT LEAST ONE | | | WEEK PRIOR TO CALLING THE ROUGH | | | INSPECTION TO INSURE THE REVIEW PROCESS | | | WILL NOT HOLD UP WORK. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|