| Plan Review Notes For Permit 04100746 |
| Permit Number |
04100746 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-04 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04100746 | | | ADD: 400 COLUMBIA DR# 101 | | | CONT: SISCA CONSTTRUCTION | | | TEL: (561)686-5545 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1) PLANAS ARE MISSING THE LOCATION OF | | | EXIT SIGNS AND OR DIRECTIONALS: | | | 1016.3.1. EXIT SIGNS: | | | EXIT SIGNS SHALL BE MARKED BY AN | | | APPROVED SIGN READILY VISIBLE FROM ANY | | | DIRECTION OF EXIT ACCESS. EVERY EXIT | | | SIGN SHALL BE SUITABLE ILLUMINATED BY A | | | RELIABLE LIGHT SOURCE. EXTERNALLY AND | | | INTERNALLY ILLUMINATED SIGNS SHALL BE | | | VISIBLE IN BOTH THE NORMAL & EMERGENCY | | | LIGHTING. | | | | | | 2) 704.2.1.4 CORRIDOR PARTITIONS, | | | SMOKE STOP PARTITIONS, HORIZONTAL EXIT | | | PART- ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|