Plan Review Notes
Plan Review Notes For Permit 04100740
Permit Number 04100740
Review Stop E
Sequence Number 2
Notes
Date Text
2005-01-14 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULE AND SHOW
 WINDOW RECEPTS.
 PLEASE SEE OUTSIDE LIGHTS SHOWN ON SHOW
 WINDOW CIRCUIT? NO OTHER LOADS ARE
 PERMITTED ON THIS.210.62,220.12
 **NOTE** PLEASE SEE PLANS INDICATE (7)
 SEPARATE CIRCUITS FOR SHOW WINDOWS?
  
 2)NOTE: PLEASE SEE PLANS SHOW PANEL IN
 STORAGE AREA. PLEASE SEE 408.7, AND
 110.26. PLANS NEED TO INDICATE CLEARENCE
 AND AREA TO BE PAINTED ON FLOOR INFRONT
 OF PANEL.
  
 3)NOTE: PLEASE SEE SEC'S SHOWN AS 110
 THWN? IS THIS SUPPOSE TO BE 1/0'S?
 MISPRINT ON PLANS.
  
  
 *** PLEASE SEE THAT THESE MAY BE DONE AS
 A "PROVISO" IF PLANS DO NOT COME BACK
 FOR ANY OTHER COMMENTS.****
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717