| Plan Review Notes For Permit 04100740 |
| Permit Number |
04100740 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-01-14 00:00:00 | ******** UNSAT ********* | | | | | | 1)NOTE: PLEASE CORRELATE CIRCUITING ON | | | PLANS WITH PANEL SCHEDULE AND SHOW | | | WINDOW RECEPTS. | | | PLEASE SEE OUTSIDE LIGHTS SHOWN ON SHOW | | | WINDOW CIRCUIT? NO OTHER LOADS ARE | | | PERMITTED ON THIS.210.62,220.12 | | | **NOTE** PLEASE SEE PLANS INDICATE (7) | | | SEPARATE CIRCUITS FOR SHOW WINDOWS? | | | | | | 2)NOTE: PLEASE SEE PLANS SHOW PANEL IN | | | STORAGE AREA. PLEASE SEE 408.7, AND | | | 110.26. PLANS NEED TO INDICATE CLEARENCE | | | AND AREA TO BE PAINTED ON FLOOR INFRONT | | | OF PANEL. | | | | | | 3)NOTE: PLEASE SEE SEC'S SHOWN AS 110 | | | THWN? IS THIS SUPPOSE TO BE 1/0'S? | | | MISPRINT ON PLANS. | | | | | | | | | *** PLEASE SEE THAT THESE MAY BE DONE AS | | | A "PROVISO" IF PLANS DO NOT COME BACK | | | FOR ANY OTHER COMMENTS.**** | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|