| Plan Review Notes For Permit 04100740 |
| Permit Number |
04100740 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) PER TABLE 403.1 A DRINKING FOUNTAIN | | | IS REQUIRED. ALSO SEE SECTION 410.1 | | | IF A DRINKING FOUNTAIN IS INSTALLED, | | | SUBMIT A DETAIL SHOWING COMPLIANCE WITH | | | SECTION 11-4.15 AND ALL SUBSECTIONS | | | INCLUDING 11-4.1.3(10)(A) | | | 2) TOILET ROOM IS NOT WIDE ENOUGH. | | | MINIMUM SIZE OF A TOILET ROOM SHALL BE | | | 5'3". W/C SHALL BE 18" TO CENTER OF | | | FIXTURE TO WALL. 30" REQUIRED FROM | | | CENTER OF W/C TO C/L OF LAV. LAV TO BE | | | MIN. 15" FROM CENTER OF FIXTURE TO WALL. | | | | | | SECTION 405.3. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|