Plan Review Notes
Plan Review Notes For Permit 04100740
Permit Number 04100740
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-23 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE BLDG APPEARS TO BE A
 CHANGE IN OCCUPANCY?
 HOUSE/RES TO COMM.
  
 2)NOTE: PLEASE VERIFY LIGHTING FOR SPACE
 INSIDE. PLEASE ALSO CLARIFY EGRESS LTS
 LS 101 5-8.
 SWITCHES ARE SHOWN ON PLANS, BUT DO NOT
 APPEAR TO CONTROL ANYTHING??
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH PANEL SCHEDULE.
 PLEASE SEE 700.12E FOR EM/EXT LTS.
  
 4)NOTE: PLEASE SEE RISER SHOWS GEC GOING
 TO FOOTER STEEL. THIS IS NOT REQUIRED
 ON AN EXISTING BLDG, HOWEVER IT IS
 PERMITTED. IF SHOWN ON PLANS THEN IT
 WILL BE REQUIRED. THIS IS ONLY A NOTE:
  
 5)NOTE: PLEASE SHOW REQUIRED DISC PER
 440.11
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFECT
 ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]