2004-10-26 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW,
 PLEASE PROVIDE THE FOLLOWING:
 1.ENERGY CALCUALTIONS PER 2001
 FBC CHAPTER 13 SUB-CHAPTER 4.
  
 2.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M) 403.3.
  
 3.PLAN INDICATES AREAS SECTIONED OFF,
 ARE THESE INDIVIDUAL OFFICES?RETURN
 AIR REQUIRED FROM THESE AREAS SHOULD
 THEY BE ISOLATED FROM THE RETURN AIR.
  
 4.MECHANICAL ROOM IS INDICATED ON
 THE PLAN WITH A "FREE RETURN" THROUGH
 A LOUVERED DOOR.THIS AREA CANNOT BE
 USED FOR STORAGE AND SHALL COMPLY WITH
 2001 FBC CHAPTER 13 SUB-SECTION
 410.1.ABCD.3.7 (MECHANICAL CLOSETS).
  