| Plan Review Notes For Permit 04100738 |
| Permit Number |
04100738 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-26 00:00:00 | DENIED: | | | INSUFFICIENT INFORMATION FOR REVIEW, | | | PLEASE PROVIDE THE FOLLOWING: | | | 1.ENERGY CALCUALTIONS PER 2001 | | | FBC CHAPTER 13 SUB-CHAPTER 4. | | | | | | 2.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) 403.3. | | | | | | 3.PLAN INDICATES AREAS SECTIONED OFF, | | | ARE THESE INDIVIDUAL OFFICES?RETURN | | | AIR REQUIRED FROM THESE AREAS SHOULD | | | THEY BE ISOLATED FROM THE RETURN AIR. | | | | | | 4.MECHANICAL ROOM IS INDICATED ON | | | THE PLAN WITH A "FREE RETURN" THROUGH | | | A LOUVERED DOOR.THIS AREA CANNOT BE | | | USED FOR STORAGE AND SHALL COMPLY WITH | | | 2001 FBC CHAPTER 13 SUB-SECTION | | | 410.1.ABCD.3.7 (MECHANICAL CLOSETS). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|