| Plan Review Notes For Permit 04100733 |
| Permit Number |
04100733 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A4.0 SANITARY RISER DIAGRAM, 2" | | | HUB DRAIN SHALL NOT CONNECT AS A "SAFE | | | WASTE" AND SHALL HAVE ITS OWN TRAP. HUB | | | DRAIN SHALL CONNTEC TO THE VENTED LINE | | | A | | | MAXIMUM OF 6 FEET FROM VENTED LINE. | | | SECTION 912.2 AND TABLE 906.1. | | | 2) SUBMIT CALCULATIONS FOR MINIMUM | | | FIXTURE FACILITIES. SHOW EXISTING | | | TOILET | | | ROOMS AND INDICATE NUMBER OF EXISTING | | | W/C'S, URINALS, LAV'S ECT. - INDICATE | | | EXISTING SEATING, AND SQUARE FOOTAGE OF | | | BUILDING. SHOW NEW TOTALS FOR SQUARE | | | FOOTAGE AND SEATING. INDICATE IF | | | SEATING | | | IS FIXED OR NOT FIXED. TABLES 1003.1 | | | AND | | | 403.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|