Plan Review Notes
Plan Review Notes For Permit 04100733
Permit Number 04100733
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A4.0 SANITARY RISER DIAGRAM, 2"
 HUB DRAIN SHALL NOT CONNECT AS A "SAFE
 WASTE" AND SHALL HAVE ITS OWN TRAP. HUB
 DRAIN SHALL CONNTEC TO THE VENTED LINE
 A
 MAXIMUM OF 6 FEET FROM VENTED LINE.
 SECTION 912.2 AND TABLE 906.1.
 2) SUBMIT CALCULATIONS FOR MINIMUM
 FIXTURE FACILITIES. SHOW EXISTING
 TOILET
 ROOMS AND INDICATE NUMBER OF EXISTING
 W/C'S, URINALS, LAV'S ECT. - INDICATE
 EXISTING SEATING, AND SQUARE FOOTAGE OF
 BUILDING. SHOW NEW TOTALS FOR SQUARE
 FOOTAGE AND SEATING. INDICATE IF
 SEATING
 IS FIXED OR NOT FIXED. TABLES 1003.1
 AND
 403.1.
  
  