| Plan Review Notes For Permit 04100733 |
| Permit Number |
04100733 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-25 00:00:00 | ****** UNSAT ****** | | | | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS. PLEASE SEE EM/EXT LTS. 700.12E | | | | | | 2)NOTE: PLEASE CLARIFY LIGHTING IN THE | | | NEW BAR AREA. COULD NOT LOCATE ANY NEW | | | LIGHTING? | | | DO FANS CONTAIN LTS?LS101 5-8 | | | | | | 3)NOTE: PLEASE SEE RISER DIAGRAM SHOWS | | | A 3P-60A BRKR TO FEED NEW PANEL, YET | | | PLANS SHOWS/NOTES A 2P-60A? | | | PANEL SCHEDULE INDICATES A 3-PHASE PANEL | | | | | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWERS WHICH MAY HAVE AN AFFECT | | | ON ELECTRICAL PLANS. | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | ONLY INSERT NEW SHEETS INTO COMPLETE | | | SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|