| Notes |
| Date |
Text |
| 2004-11-05 00:00:00 | PROVISO: | | | 1.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 2.ACCESS TO THE AHU IN THE MAIN HOUSE | | | SHALL COMPLY WITH 2001 FBC CHAPTER 13 | | | SECTION 610.1.ABC.3.5.2. | | | | | | 3.PLEASE NOTE, AHU LOCATED IN THE | | | GUEST HOUSE.MECHANICAL CLOSET SHALL | | | COMPLY WITH 2001 FBC CHAPTER 13 SECTION | | | 610.1.ABC.3.7.PLAN SHEET A-2 INDICATES | | | THE ROOM WHERE THE AHU IS LOCATED IS FOR | | | "STORAGE", THEREFORE THE AHU CANNOT HAVE | | | A FREE RETURN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @(561)805-6719. |
|