Plan Review Notes
Plan Review Notes For Permit 04100627
Permit Number 04100627
Review Stop P
Sequence Number 1
Notes
Date Text
2004-11-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1) TABLE 403.1 A DRINKING FOUNTAIN IS
 REQUIRED. ALSO SEE SECTION 410.1
 2) SHT P1 WATER RISER DIAGRAM, SHOW
 REQUIRED WATER HAMMMER ARRESTORS AT THE
 WASH MACHINE. SECTION 604.9
 3) SHT P1 PLUMBING SPECIFICATIONS #14,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 104.2.1
 4) SHT P1 SANITARY RISER DIAGRAM, ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUP
 SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ADDITIONAL
 FIXTURES (WASH MACHINE) SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTION
 909.1
 5) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE FOR THIS SPACE. 608.13.2
 BACKFLOW SHALL BE MAXIMUM 4' ABOVE THE
 FLOOR FOR CERTIFICATION & SERVICE.
 6) 61G1-16.004(2) THE FIRM LICENSE
 NUMBER IS REQUIRED. (CERTIFICATE OF
 AUTHORIZATION). FS 481.219
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved