| Plan Review Notes For Permit 04100627 |
| Permit Number |
04100627 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1) TABLE 403.1 A DRINKING FOUNTAIN IS | | | REQUIRED. ALSO SEE SECTION 410.1 | | | 2) SHT P1 WATER RISER DIAGRAM, SHOW | | | REQUIRED WATER HAMMMER ARRESTORS AT THE | | | WASH MACHINE. SECTION 604.9 | | | 3) SHT P1 PLUMBING SPECIFICATIONS #14, | | | AIR CHAMBERS ARE NOT APPROVED. DELETE | | | REFERENCE. SECTION 104.2.1 | | | 4) SHT P1 SANITARY RISER DIAGRAM, ONLY | | | THE FIXTURES WITHIN THE BATHROOM GROUP | | | SHALL CONNECT TO THE WET-VENTED | | | HORIZONTAL BRANCH DRAIN. ADDITIONAL | | | FIXTURES (WASH MACHINE) SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SECTION | | | 909.1 | | | 5) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE FOR THIS SPACE. 608.13.2 | | | BACKFLOW SHALL BE MAXIMUM 4' ABOVE THE | | | FLOOR FOR CERTIFICATION & SERVICE. | | | 6) 61G1-16.004(2) THE FIRM LICENSE | | | NUMBER IS REQUIRED. (CERTIFICATE OF | | | AUTHORIZATION). FS 481.219 | | | | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|