2004-11-04 00:00:00DENIED:
 1.PLEASE PROVIDE SUBMITTAL DATA FOR
 THE MANUFACTURED CONDENSIGN UNIT STAND.
 THE STAND SHALL COMPLY WITH 2001 FBC
 1511.7 FOR THE HEIGHT REQUIREMENT FROM
 THE ROOF SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL.
  
 2.CLARIFY THE BOOTH AREA.DOES THE
 WALL SEPARATION BETWEEN THE BOOTHS
 EXTEND FROM THE FLOOR TO THE CEILING OR
 IS THIS A "PARTITION" THAT DOES NOT
 EXTEND TO ISOLATE EACH BOOTH AREA.
 RETURN AIR IS REQUIRED FROM ALL
 HABITABLE ROOMS SEPARATED BY A DOOR AND
 WALLS FROM THE RETURN PER 2001 FBC(M)
 601.4.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFCATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER 2001
 FBC(M) 606.4.1.
  
 4.SEE ALSO COMMENT #1 BY DEWEY PALMER,
 ELECTRICAL PLANS EXAMINER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @(561) 805-6719.