| Plan Review Notes For Permit 04100627 |
| Permit Number |
04100627 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-04 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE SUBMITTAL DATA FOR | | | THE MANUFACTURED CONDENSIGN UNIT STAND. | | | THE STAND SHALL COMPLY WITH 2001 FBC | | | 1511.7 FOR THE HEIGHT REQUIREMENT FROM | | | THE ROOF SURFACE TO THE BOTTOM OF THE | | | SUPPORT RAIL. | | | | | | 2.CLARIFY THE BOOTH AREA.DOES THE | | | WALL SEPARATION BETWEEN THE BOOTHS | | | EXTEND FROM THE FLOOR TO THE CEILING OR | | | IS THIS A "PARTITION" THAT DOES NOT | | | EXTEND TO ISOLATE EACH BOOTH AREA. | | | RETURN AIR IS REQUIRED FROM ALL | | | HABITABLE ROOMS SEPARATED BY A DOOR AND | | | WALLS FROM THE RETURN PER 2001 FBC(M) | | | 601.4. | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | SHALL HAVE NOTIFCATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS PER 2001 | | | FBC(M) 606.4.1. | | | | | | 4.SEE ALSO COMMENT #1 BY DEWEY PALMER, | | | ELECTRICAL PLANS EXAMINER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @(561) 805-6719. |
|