| 2004-10-28 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04100627 |
| | ADD: 7750 OKEECHOBEE BLVD# 3 |
| | CONT: PLAN REVIEW/ SPANISH RIVER |
| | TEL: (561)723-9714 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) 481.219/ FAC 61G1-16.004 LICENSE |
| | NUMBERS REQUIRED ON TITLE BLOCK. |
| | |
| | 3) 11-4.3.3. WIDTH. THE MINIMUM CLEAR |
| | WIDTH OF AN ACCESSIBLE ROUTE SHALL BE |
| | 36". IF A PERSON IN A WHEELCHAIR MUST |
| | MAKE A TURN AROUND AN OBSTRUCTION, THE |
| | MINIMUM CLEAR WIDTH OF THE ACCESSIBLE |
| | CLEAR ROUTE SHALL BE AS SHOWN IN FIGURE |
| | 7A AND 7B. |
| | |
| | 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| | STOP PARTITIONS, HORIZONTAL EXIT PART- |
| | ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | BUILDING PLAN REVIEW |