Plan Review Notes
Plan Review Notes For Permit 04100617
Permit Number 04100617
Review Stop P
Sequence Number 2
Notes
Date Text
2004-12-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1) SHT A-1 WATER RISER DIAGRAM SHOWS TWO
 1/2" LINES TO A FIXTURE NOT SHOWN ON THE
 FLOOR PLAN, AND NOW SAYS WATER HAMMER
 ARRESTORS. PLEASE INDICATE WHAT THE
 LINES SUPPLY. SECTION 104.2.1
 2) SHT A-1 WATER HEATER SHALL BE
 ACCESSIBLE. OPENING IN THE CABINET DOES
 NOT APPEAR TO BE LARGE ENOUGH TO REMOVE
 THE WATER HEATER. SUPPLY MEASUREMENTS
 FOR THE WATER HEATER AND THE DOOR
 OPENING. SECTIONS 104.2.1 & 501.4
 3) KITCHEN SINK SHALL BE ACCESSIBLE.
 SUBMIT A DETAIL SHOWING KNEE CLEARANCE
 11-4.24.3, SINK DEPTH 11-4.24.4, CLEAR
 FLOOR SPACE (FORWARD APPROACH) FIG 32,
 AND SECTION 11-4.24.5, AND EXPOSED PIPES
 AND SURFACES 11-4.24.6.
 4) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESSM AND LICENSE NUMBER
 ON EACH SHEET. FAC 61G15-23.--2(2) AND
 FS 471..025
 *******NEW COMMENT*******
 1B) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS
 553.80(2)(B).
  
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]