Plan Review Notes
Plan Review Notes For Permit 04100617
Permit Number 04100617
Review Stop E
Sequence Number 2
Notes
Date Text
2004-11-18 00:00:00*********** UNSAT ***********
  
 ***PLEASE SEE PACKAGE DID NOT COME BACK
 WITH ORIGINAL PERMIT APPLICATION ?? ***
  
 1)NOTE: PLEASE CORRELATE A/C HEAT LOAD
 WITH MECH PLANS.
 ONE SHOWS 10KW AND THE OTHER 8KW?
  
 2)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM LTS. SHOWN ON W/ OFFICE
 LTS.
  
 3)NOTE: PLEASE SEE MISSING RECEPT FOR
 ROOFTOP A/C 210.63 GFI
  
 4)NOTE: PLEASE SEE PLANS ARE NOT
 PERMITTED TO HAVE ANY HANDWRITTEN
 CHANGES OR ADDITIONS TO PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN
 ENGINEER.
 FS 471.025
  
 ** PLEASE SEE TITLE BLOCK MENTIONS TED
 BERGUS CONTRACTOR, YET PERMIT
 APPLICATION IS FOR BAINES BLDG??
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]