2005-03-24 00:00:00FEEDERS REVISED TO SHOW SE CABLE,
 HOWEVER PLANS/RISER STILLS SHOWS BEING
 INSTALLED IN CONDUIT. CALLED ELECTRICAL
 ENGINEER,CONDUIT IS NOT BEING USED. THIS
 IS A MISPRINT ON PLANS.
 CONDUIT CROSSED OUT ON PLANS PER
 ENGINEER'S REQUEST.
  
  
 WASHER VA REDLINED, SHOULD BE 1500VA
 220.16
  
 IF PLANS ARE REVISED FOR ANY FUTURE
 ITEMS, PLEASE ADJUST THE ABOVE AT THAT
 TIME.