| Notes |
| Date |
Text |
| 2004-11-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT 1 CLEAR FLOOR SPACE FOR BREAK | | | ROOM SINK SHALL BE FORWARD APPROACH NOT | | | PARALLEL AS SHOWN. SECTION 11-4.24.5. | | | 2) SHT 2 SHOW CLEAR FLOOR SPACE FOR | | | SINK. SECTION 11-4.24.5. | | | 3) SHT 7 IN THE INSTALLATION OR REMOVAL | | | OF ANY PART OF A DRAINAGE SYSTEM, DEAD | | | ENDS SHALL BE PROHIBITED. | | | 4) SHT 8 (SEE COMMENT #3). | | | 5) SUBMIT A DETAIL FOR THE SINKS SHOWING | | | COMPLIANCE WITH SECTION 11-4.24 AND ALL | | | SUBSECTIONS. SHOW: | | | A) HEIGHT 11-4.24.2 | | | B) KNEE CLEARANCE 11-4.24.3 | | | C) DEPTH OF SINK 11-4.24.4 | | | D) CLEAR FLOOR SPACE - WHICH SHALL BE | | | PROVIDED IN FRONT OF A SINK TO ALLOW | | | FORWARD APPROACH AND SHALL EXTEND A | | | MAXIMUM OF 19" UNDERNEATH THE SINK. | | | E) EXPOSED PIPES AND SURFACES | | | 11-4.24.6 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|