| 2005-06-02 00:00:00 | ****DENIED**** | | | | | | 1) AT 8 STORIES IN HEIGHT, IT WOULD | | | APPEAR THAT THIS BUILDING MEETS THE | | | DEFINITION OF A HIGHRISE STRUCTURE. | | | PLEASE CLARIFY. | | | | | | 2) PLEASE ILLUSTRATE HOW THE NFPA 72 | | | REQUIREMENT FOR SURVIVABILITY WILL BE | | | MET. | | | | | | 3) HORNSTROBES AND SPEAKERS APPEAR TO BE | | | MISSING IN THE CORRIDORS AT THE PARTIAL | | | 2ND GROUND FLOOR LEVEL, SHEETS # 12&13. | | | | | | 4) PLEASE PROVIDE FURTHER EXPLANATION IN | | | REGARDS TO WHAT DEVICES WILL ACTIVATE | | | STAIRWELL PRESSURIZATION. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2951 OR 805-6722 |
|