| 2004-10-25 00:00:00 | *******DENIED*************************** | | | | | | 1) NEW FIRE ALARM SYSTEMS SHALL BE | | | LISTED FOR CENTRAL STATION SERVICE. | | | | | | 2) ALL NEW FIRE ALARM SYSTEMS THAT | | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | | BE UL CERTIFICATED AND HAVE DOCUMENT | | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | | FINAL APPROVAL OF THE FIRE ALARM SYSTEM. | | | | | | 3) THE WEST PALM BEACH FIRE MARSHAL | | | OFFICE REQUIRES DUCT DETECTORS TO SEND | | | A GENERAL FIRE ALARM NOT A SUPERVISORY. | | | | | | 4) THE FIRE ALARM SYSTEM SHALL BE | | | CLASS "A" OR FULLY ADDRESSABLE. | | | | | | | | | NATE MCCRAY, CAPTAIN | | | 561-835-2910 OR 561-805-6722 |
|