| Notes |
| Date |
Text |
| 2004-10-28 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | 1. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2001 FUEL | | | GAS CODE SECTION 304. - SEE DRYER ROOM, | | | WATER HEATER ROOM, AND FIREPLACE. | | | 2) SHUTOFF VALVES ARE REQUIRED UPSTREAM | | | OF THE GAS REGULATORS. SECTION 409.7 | | | SHOW ON GAS RISER DIAGRAM. | | | 3) ALL DRAWINGS SHALL BEAR THE NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. SECTION 104.2.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|