| Plan Review Notes For Permit 04100446 |
| Permit Number |
04100446 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-11-21 15:19:21 | DENIED; | | | | | | 1. RISER DIAGRAM DOES NOT MATCH FLOOR PLANS. BATHROOMS | | | ARE BACK TO BACK . EATHER CHANGE THE BATHROOM PIPING OR | | | THE BUILDING DRAIN. | | | 2. RISER DIAGRAM SHOWS MORE BATHROOMS THAN ARE SHOWN ON | | | FLOOR PLAN. | | | 3. MOP SINK CANNOT BE PART OF THE BATHROOM WET VENT SEE | | | FBC-2001 PLUMBING SECTION 909.1. | | | 4. AS NOTED ON APPROVED PLUMBING PAGE A PROVISO WAS | | | NOTED THAT ONE 3" STACK IS REQUIRED FOR EACH BUILDING. | | | NOT SHOWN ON REVISED SANITARY RISER DIAGRAM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|