Plan Review Notes
Plan Review Notes For Permit 04100446
Permit Number 04100446
Review Stop P
Sequence Number 5
Notes
Date Text
2006-11-21 15:19:21DENIED;
  
 1. RISER DIAGRAM DOES NOT MATCH FLOOR PLANS. BATHROOMS
 ARE BACK TO BACK . EATHER CHANGE THE BATHROOM PIPING OR
 THE BUILDING DRAIN.
 2. RISER DIAGRAM SHOWS MORE BATHROOMS THAN ARE SHOWN ON
 FLOOR PLAN.
 3. MOP SINK CANNOT BE PART OF THE BATHROOM WET VENT SEE
 FBC-2001 PLUMBING SECTION 909.1.
 4. AS NOTED ON APPROVED PLUMBING PAGE A PROVISO WAS
 NOTED THAT ONE 3" STACK IS REQUIRED FOR EACH BUILDING.
 NOT SHOWN ON REVISED SANITARY RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695