2005-08-28 00:00:00PLUMBING PLAN REVIEW EXAMINER, FBC 2001
 PAUL SCHMITZ561-805-6692
  
 [email protected]
 FBC- P2001
 FBC- B2001
 DENIED
 1.)SHT P-1, TYPICAL, 3" VTR THRU 8" BEAM
 NOT APPROVED
 ?1907.3.5 EXCEPT WHEN PLANS FOR
 CONDUITS AND PIPES ARE APPROVED BY THE
 ENGINEER, CONDUITS AND PIPES EMBEDDED
 WITHIN A SLAB, WALL OR BEAM (OTHER
 THAN THOSE MERELY PASSING THROUGH)
 SHALL SATISFY THE FOLLOWING:
 1. THEY SHALL NOT BE LARGER IN
 OUTSIDE DIMENSION THAN ONE-THIRD THE
 OVERALL THICKNESS OF SLAB, WALL OR
 BEAM IN WHICH THEY ARE EMBEDDED.
 2. THEY SHALL NOT BE SPACED CLOSER
 THAN THREE DIAMETERS OR WIDTHS ON
 CENTER.
 3. THEY SHALL NOT IMPAIR
 SIGNIFICANTLY THE STRENGTH OF THE
 CONSTRUCTION.
  
 2.)SHT P-1, TYPICAL, WATER RISER:
 TABLE 604.5, MINIMUM SIZE OF FIXTURE
 WATER SUPPLY, 1/2"
  
 3.)SHT P-1 PREVIOUS NOTE:
 "EXAMLPE PROVIDED"
 SHT P-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS. NO FITTINGS
 APPROVED AS SHOWN ON RISER. SEE EXAMPLE
 OF TYPICAL BACK-TO-BACK AND SINGLE
 TOILET ROOM PIPING FOR RISER.
  
 4.) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  
 END OF COMMENTS