Plan Review Notes For Permit 04100446
Permit Number 04100446
Review Stop P
Sequence Number 2
Notes
Date Text
2005-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. SHTS A-1 THRU A-4 A SERVICE SINK IS
 REQUIRED IN EACH SPACE PER TALBE 403.1.
 - NO RESPONSE, COMMENT NOT ADDRESSED.
 ****************NEW COMMENT*************
 1B. SEAL SHALL CONTAIN THE INFORMATION
 REQUIRED BY FAC 61G1-16.002 AND THIS
 INFORMATION SHALL BE IMPRESSED ON EACH
 SHEET. FS 481.221 - NO INFORMATIONS CAN
 BE GLEANED FROM THE SEAL.
 2B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  