| Plan Review Notes For Permit 04100446 |
| Permit Number |
04100446 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-13 00:00:00 | ************* UNSAT ********* | | | | | | 1)NOTE: PLEASE SEE NOTE #2 FROM PREVIOUS | | | REVIEW. | | | | | | 2)NOTE: PLEASE SEE SEC'S BLDG -1, SHOWS | | | 250MCM FOR 600A SERVICE W/ 300A FUSES. | | | PLEASE SEE 310.16,240.4. FOR MIN SEC'S. | | | PLEASE CORRELATE SEC SIZING WITH LOAD AS | | | SHOWN ON LOAD CALCULATIONS. | | | | | | 3)NOTE: PLEASECLARIFY NOTE AT LOWER | | | LEFT OF BLDG'S #3 AND #4 RISER: | | | NOTE: NO 3 0. - ALL 1 0 22KAIC.????? | | | | | | 4)NOTE: PLEASE SEE ALL SUB PANELS ARE | | | SHOWN AS MLB? PLEASE CLARIFY IF THESE | | | PANELS ARE MCB(MAIN CIRCUIT BRKR) OR | | | MLO( MAIN LUG ONLY)? | | | | | | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | | PLEASE ONLY INSERT NEW REVISED SHEETS | | | INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | PLEASE SEE ANY OTHER COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | |
|