| Plan Review Notes For Permit 04100446 |
| Permit Number |
04100446 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHTS A-1 THRU A-4 A SERVICE SINK IS | | | REQUIRED IN EACH SPACE PER TABLE 403.1 | | | 2) SHT P-1 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS. NO FITTINGS | | | APPROVED AS SHOWN ON RISER. SEE EXAMPLE | | | OF TYPICAL BACK-TO-BACK AND SINGLE | | | TOILET ROOM PIPING FOR RISER. | | | 2) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SUPPLY TO THE BLDG. SECTION | | | 608.13.2 | | | 3) INDICATE IF WATER RISER IS OVERHEAD | | | OR UNDERGROUND. SECTION 104.2.1 | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|