Plan Review Notes
Plan Review Notes For Permit 04100446
Permit Number 04100446
Review Stop M
Sequence Number 1
Notes
Date Text
2004-11-04 00:00:00DENIED:
 1.PLAN SHEET SP-1 DRAWING INDEX, PLANS
 S-5 THROUGH S-8 ARE NOT INCLUDED WITH
 SUBMITTAL.
  
 2.ENERGY CALCULATIONS ARE REQUIRED PER
 2001 FBC CHAPTER 13 IN ACCORDANCE WITH
 CHAPTER 4.
  
 3.PROVIDE MECHANICAL PLANS.PLEASE
 INDCLUDE THE FOLLOWING:
 1) EQUIPMENT SCHEDULE
 2) LOCATION OF EQUIPMENT.
 3) PROVIDE DETAIL OR MANUFACTURER
 SUBMITTAL/INSTALLATION INSTRUCTIONS
  
 FOR ANY CURBS OR STANDS LOCATED ON
 THE ROOF.
 4) INDICATE CONDENSATE LINE SIZE,
 TERMINATION & PIPE MATERIAL.
 5) INDICATE ACCESS TO ROOF.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS @ (561)805-6719
  