| Plan Review Notes For Permit 04100446 |
| Permit Number |
04100446 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-05 00:00:00 | 1) BUILDING ADDRESSES REQUIRED. A | | | MINIMUM OF AT SIX HIGH NUMBERS ARE | | | REQUIRED. | | | | | | 2) WHAT TYPES OF COMMODITIES WILL | | | BE STORED IN THE BUILDING. ANY | | | FLAMMABLE | | | GASES, LIQUIDS OR SOLIDS PLANNED TO | | | BE STORED. ANY COMBUSTIBLES LIQUIDS | | | OR SOLIDS PLANNED. ALSO ANY HAZARDOUS | | | CHEMICALS PLANNED. | | | | | | 3) TENANT SEPARATION WALLS REQUIRED | | | BETWEEN TENANTS IF DIFFERENT. | | | | | | 4) PLEASE PROVIDE INFORMATION ON | | | HOURLY RATINGS FOR DEMISING WALLS. | | | | | | 5) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 6) NO MENTION OF ANY PORTABLE FIRE | | | EXTINGUISHERS. | | | | | | 7) A FIRE ALARM SYSTEM MAY BE REQUIRED | | | IF EXCEPTIONS OF THE CODE CANNOT | | | BE MET. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|