Plan Review Notes
Plan Review Notes For Permit 04100446
Permit Number 04100446
Review Stop E
Sequence Number 1
Notes
Date Text
2004-10-27 00:00:00********** UNSAT ***********
  
 1)NOTE:PLEASE SEE PLANS ARE NOT COMPLETE
 AT THIS TIME FOR COMPLETE REVIEW.
 PLEASE SUBMIT SERVICE(S) RISER,PANEL
 SCHEDULES, GROUNDING ETC.
 215.5
  
 2)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY A PE.
 UNDER FS 471.003H1
  
 3)NOTE: PLANS NOTE: ALL EM/EXT LTS
 CIRCUITED W/ LOCAL BRANCH CIRCUIT,HOW-
 -EVER THESE APPEAR TO BE SHOWN ON OTHER
 CIRCUITS AND UNABLE TO VERIFY AT THIS
 TIME. (NO PANEL SCHEDULES)
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) AS IT MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 DUE TO PLANS NOT BEING COMPLETE AT THIS
 TIME, THERE MAY BE OTHER COMMENTS ON
 NEXT REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]