| 2004-11-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04100446 |
| | ADD: NOT YET ASSIGNED |
| | PCN: 74-43-43-09-11-003-0000 |
| | CONT: COMPLETE PROPERTY MANAGEMENT |
| | TEL: (561)252-8372 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | INDICATE COMPLIANCE WITH 1804.2.2 |
| | QUESTIONABLE SOILS, ALLTERRA REPORT |
| | DATED MARCH 5/ 2004 INDICATES THAT PEAT |
| | |
| | WAS DISCOVERED WITH BORING# 2, SHOW HOW |
| | YOU WILL COMPLY WITH THIS SECTION? |
| | |
| | 2) FOR BUILDING# 1 & BUILDING# 2, SHOW |
| | COMPLIANCE WITH TABLE 500 FOR STORAGE: |
| | A) BUILDING# 1 TABLE 500 FOR TYPE IV, |
| | UNPROTECTEDIF TAKING GENERAL AREA |
| | MODIF- |
| | ICATIONS YOU CAN ONLY TAKE THE AREA |
| | UNDER COLUMN(H)@ 100% THE AREA INCREASE |
| | WILL BRING YOU TO 32,000 SQ FT SHORT OF |
| | THE 35,123 SQ FT REQUIRED. ADDITIONAL |
| | OCCUPANCY MODIFICATIONS FOR STORAGE CAN |
| | BE TAKEN IF FIRE SPRINKLERS FOR STORAGE |
| | |
| | OCCUPANCY ARE INSTALLED. THERE IS AN |
| | EXCEPTION WITHA CLEAR 60' AREA AROUND |
| | THE STRUCTURE BUT WITH HAVING MORE THAN |
| | |
| | ONE TENANT THE EXCEPTION CAN NOT BE |
| | TAKEN BECAUSE OF NONCOMBUSTIBLE |
| | PRODUCTS |
| | AND WRAPPINGS CONTAINERS AND PALLETS. |
| | B) BUILDING# 2 CAN TAKE THE AREA |
| | INCRESE |
| | ON THREE SIDES, THE AREA INCREAS IS |
| | 38.13% OF THE NON SPRINKLERED AREA OR AN |
| | |
| | ADDITIONAL 6080 SQ FT FOR A TOTAL OF |
| | 22,080 TOTAL SQ FT. |
| | C) ONE WAY TO COMPLY WITH TABLE 500 |
| | WOULD BE TO PUT A 4HR FIRE WALL |
| | CENTERED |
| | IN BOTH BUILDINGS, THIS WILL CREATE (4) |
| | BUILDINGS AND COMPLY WITH TABLE 500.IF |
| | THIS APPROACH IS CONSIDERED, SEE TABLE |
| | 709.3.1 FOR EQUIVALLENT THICKNESS OF |
| | BEARING & NONBEARING CONCRETE MASONARY |
| | WALLS. PROVIDE FROM BLOCK MANUFACTURER. |
| | |
| | 3) FBC* 105.3RESIDENT INSPECTOR. |
| | SUBMIT INSPECTOR RESUME' AND LICENSE |
| | DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF |
| | THE RESIDENT INSPECTOR PROGRAM.A |
| | RESIDENT INSPECTOR PROGRAM IS REQUIRED, |
| | ON THIS PROJECT, DUE TO ONE OR MORE OF |
| | THE FOLLOWING: |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQFT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| | OR METHODS OF CONSTRUCTION |
| | CALL HAROLD PISKURA FOR THE SPECIAL |
| | INSPECTOR PROGRAM AT 805-6711. |
| | |
| | 4)FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | SP-1 DRAWING INDEX INDICATES STRUCTURAL |
| | PLANS S1-8, PLANS SUBMITTED ARE S1-4 |
| | FOR |
| | THE FOUNDATION ONLY.THERE IS NO |
| | FONDATION, COLUMN NOR BEAM SCHEDULE. |
| | |
| | 5) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THE STRUCTURAL PLANS (S1-4) INDICATE THE |
| | |
| | USE OF 12" BLOCK FOR THE FRONT OF THE |
| | BUILDING WITH A RECESS 8"BLOCK AT THE |
| | |
| | GARAGE OPENINGS, HOW WILL THE BLOCK TIE |
| | |
| | TOGETHER, WILL A RUNNING BOND BE USED |
| | VERSES STACK BOND? |
| | |
| | 6) BLDG# 2, BACK ENTRY DOORS INDICATE A |
| | 3/4HR RATING, AS PER 705.1.1.2, THE |
| | SUBMITTED PRODUCT APPROVAL BENCHMARK |
| | EXTERIOR DOOR FL1190 IS FOR RESIDENTIAL |
| | USE, STEEL DOOR WITH WOOD DOOR JAMBS. |
| | PROVIDE THE FIRE TESTING REPORT. |
| | |
| | 7) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, SHEET# |
| | 7 DETAIL# 2 INDICATES THE HOLLOWCORE |
| | ROOF DECK SYSTEM PARARLLEL WITH THE |
| | FRONT OF THE BUILDINGS, PLANS DO NOT |
| | PROVIDE THE LENGHTS OF THE PLANKS, |
| | SHEET |
| | A-2 INDICATES 6" METAL STUD PARTITION, |
| | DOES THE ROOF PLANK SYSTEM SPAN THIS |
| | OR IS THIS A BEARING WALL? PLANS DO NOT |
| | PROVIDE INFORMATION FOR THIS PARTION, |
| | STUD GAUGE, SPACING C/C HEIGHT, DRYWALL |
| | THICKNESS, ETC... |
| | 8) PLANS DO NOT PROVIDE THE FOLLOWING |
| | INFORMATION: |
| | FL. BLD CODE 1606.1.7 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 9 FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) TRUSS ANCHORS/ WOOD/WOOD CONNECTORS |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 10) SHEET A-6, SOUTH ELEVATION INDICATES |
| | ARCHITECTURE FEATURES ABOVE THE BEAM |
| | BUT |
| | NO INFORMATION. |
| | |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |