| 2004-11-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT P-1 SANITARY RISER DIAGRAM DOES |
| | NOT MEET CODE REQUIREMENTS, NOR DOES IT |
| | REFLECT THE FLOOR PLAN. |
| | A) BAR SINK IN FAMILY ROOM NOT SHOWN ON |
| | THE RISER DIAGRAM. SECTION 104.2.1 |
| | B) VENT REQUIRED FOR EACH WASH MACHINE. |
| | SECTION 901.2.1, AND THE WASH MACHINE |
| | SHALL HAVE A CLEANOUT 4 FT. ABOVE THE |
| | FLOOR FOR ACCESS. SECTION 708.10 |
| | C) WASH MACHINE AND LAUNDRY SINK DO NOT |
| | REFLECT THE FLOOR PLAN. THE W/M SHALL BE |
| | ON THE RIGHT SIDE AND THE LAUNDRY SINK |
| | SHALL BE ON THE LEFT SIDE. SECTION |
| | 104.2.1 |
| | D) KITCHEN PREP SINK IS MISLABLED AS A |
| | BAR SINK. SECTION 104.2.1 |
| | E) LAVS IN THE MASTER BATH TO BOTH FACE |
| | INTO THE BATHROOM. SECTION 104.2.1 |
| | F) BATHROOM #2 ALL FIXTURES SHALL LOOK |
| | INTO THE SAME ROOM AS SHOWN ON THE FLOOR |
| | PLAN. SECTION 104.2.1 |
| | 2) INDICATE WHERE THE SHOWER ON THE |
| | FLOOR PLAN OUTSIDE THE CABANA BATH |
| | DRAINS TO. SECTION 104.2.1 |
| | 3) SHT P-1 GENERAL NOTES #8 AIR CHAMBERS |
| | ARE NOT APPROVED. DELETE FROM NOTES. |
| | SECTION 604.9 |
| | 4) 61G1-16.004(2) FIRM LICENSE NUMBER IS |
| | REQUIRED. (6) PRINTED NAME OF THE PERSON |
| | SEALING THE DOCUMENT REQUIRED. FS |
| | 481.2055. |
| | |
| | |