| Plan Review Notes For Permit 04100422 |
| Permit Number |
04100422 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-11-01 00:00:00 | PROVISO: | | | 1.PLAN SHEET M-2, BEDROOM 3 SUPPLY | | | DUCT SHALL BE A MAXIMUM OF 7" FOR | | | COMPLIANCE WITH 2001 FBC(M) 601.4 | | | EXCEPTION #1 & 3. | | | | | | 2.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 3.PLEASE NOTE, SHOULD GAS DRYERS BE | | | INSTALLED PROVIDE COMBUSTION AIR CALCS | | | AND INDICATE FRESH AIR AS REQUIRED PER | | | 2001 FBC(M) CHAPTER 7. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. |
|