| Date |
Text |
| 2005-01-31 00:00:00 | DENIED |
| | |
| | |
| | 1)PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. I HAVE |
| | ATTACHED THE COVER SHEET WITH THE FL# |
| | FOR THE TRACO WINDOWS, HOWEVER I DID NOT |
| | SEE ONE FOR THE POMA STORM PANELS. |
| | SUBMIT FLORIDA PRODUCT APPROVAL FOR |
| | STORM PANELS. |
| | |
| | 2) SUBMIT TWO COPIES OF A KEY PLAN AND |
| | INSDTALLATION SCHEDULE FOR THE STORM |
| | PANELS. SPECIFY THE TYPE OF MOUNT, THE |
| | TYPE OF FASTENERS AND THE FASTENER |
| | SPACING. |
| | |
| | 3) A SEPARATE PERMIT WILL BE REQUIRED |
| | FOR THE MECHANICAL SYSTEMS. SUBMIT |
| | MECHANICAL PLANS, ENERGY CALCS. AND |
| | MANUAL J CALCS. WITH APPLICATION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |