| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1) LAUNDRY CIRCUIT LOAD. A LOAD OF NOT |
| | LESS THAN 1500 VOLT-AMPERES SHALL BE |
| | INCLUDED FOR EACH 2-WIRE LAUNDRY BRANCH |
| | CIRCUIT INSTALLED AS REQUIRED BY |
| | 210.11(C)(2). THIS LOAD SHALL BE |
| | PERMITTED TO BE INCLUDED WITH THE |
| | GENERAL LIGHTING LOAD AND SUBJECTED TO |
| | THE DEMAND FACTORS PROVIDED IN TABLE |
| | 220.11. |
| | |
| | 2} 220.18 ELECTRIC CLOTHES DRYERS |
| | DWELLING UNIT(S). |
| | THE LOAD FOR HOUSEHOLD ELECTRIC CLOTHES |
| | DRYERS IN A DWELLING UNIT(S) SHALL BE |
| | 5000 WATTS (VOLT-AMPERES) OR THE |
| | NAMEPLATE RATING, WHICHEVER IS LARGER, |
| | FOR EACH DRYER SERVED. |
| | |
| | 3} 110.9 INTERRUPTING RATING. |
| | EQUIPMENT INTENDED TO INTERRUPT CURRENT |
| | AT FAULT LEVELS SHALL HAVE AN |
| | INTERRUPTING RATING SUFFICIENT FOR THE |
| | NOMINAL CIRCUIT VOLTAGE AND THE CURRENT |
| | THAT IS AVAILABLE AT THE LINE TERMINALS |
| | OF THE EQUIPMENT. |
| | |
| | 4} THE LOCATION OF THE ELECTRICAL |
| | SERVICE EQUIPMENT IS IN VIOLATION OF |
| | ARTICLE 110.26 WITH RELATIONSHIP TO THE |
| | STEPS. |
| | |
| | 6} SEE ARTICLE 210.52(E) FOR OUTSIDE |
| | RECEPTACLE REQUIREMENTS. |
| | |