| Plan Review Notes For Permit 04100365 |
| Permit Number |
04100365 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-10-20 00:00:00 | PROVISO: | | | REMOTE CONDENSER LOCATED ON THE ROOF, | | | SHALL COMPLY WITH 2001 FBC 1511.7 FOR | | | CLEARANCE BETWEEN THE ROOF SURFACE AND | | | THE BOTTOM OF THE SUPPORT RAIL. | | | | | | WIDTH OF MECHMINIMUM CLEARANCE | | | UNITABOVE THE ROOF | | | (INCHES)SURFACE (INCHES) | | | ---------------------------------------- | | | < 2414 | | | 24 < 36 18 | | | 36 < 48 24 | | | 48 < 60 30 | | | > 60 48 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|