| 2004-12-15 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1) SHTS P1 AND P3 FLOOR PLAN AND SANT. |
| | RISER DIAGRAM DO NOT MEET CODE. FROM |
| | PREVIOUS REVIEW, EVERY DRY VENT SHALL |
| | RISE VERTICALLY TO A MINIMUM OF 6 INCHES |
| | ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST |
| | TRAP OR TRAPPED FIXTURE BEING VENTED. |
| | SECTION 905.4. - STILL SHOWN ON THE |
| | FLOOR PLAN AND THE RISER DIAGRAM ARE |
| | HORIZONTAL DRY VENTS BELOW THE FLOOD |
| | LEVEL RIM OF THE W/C'S, TUBS, SHOWERS. |
| | THE PLANS SHALL REFLECT THE INSTALLATION |
| | OF THE PLUMBING. PLEASE SUBMIT A |
| | PLUMBING FLOOR PLAN AND SANT. RISER |
| | DIAGRAM THAT MEET THE CODE REQUIREMENT. |
| | SECTION 104.2.1. |
| | 2) RESPONSE TO COMMENT #2 STATES "THERE |
| | IS CURRENTLY NO GAS SERVICE TO THE |
| | HOUSE". COMMENT 2D STATES "GAS LOAD |
| | EXISTING=130,000 BTU" PLEASE CLARIFY. |
| | SHOW EXISTING GAS CONNECTION TO THE |
| | PIPING OFF THE METER. PLEASE CLARIFY |
| | SECTION 104.2.1. |
| | 3) BY NOT SHOWING THE DISTANCE FROM THE |
| | METER TO THE JACUZZI, WHEN THAT PIPE IS |
| | ADDED TO THE SYSTEM, THE PIPING FROM THE |
| | METER WILL HAVE TO BE CHANGED TO ACCOUNT |
| | FOR THE TOTAL DEVELOPED LENGTH OF THE |
| | SYSTEM. IF THIS IS SHOWN ON THE RISER |
| | DIAGRAM THE PIPE CAN BE SIZED FOR FUTURE |
| | APPLIANCES WHEN INSTALLED AT THIS TIME. |
| | TABLE 402(2). |
| | 4) SUBMIT TWO SETS OF PLANS FOR REVIEW. |
| | REMOVE ALL VOIDED SHEETS AND RESUBMIT |
| | ONE SET FOR COMPAIRISON. SECTION |
| | 104.2.1 |
| | |
| | |
| | |