Notes
Date Text
2004-12-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) SHTS P1 AND P3 FLOOR PLAN AND SANT.
 RISER DIAGRAM DO NOT MEET CODE. FROM
 PREVIOUS REVIEW, EVERY DRY VENT SHALL
 RISE VERTICALLY TO A MINIMUM OF 6 INCHES
 ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST
 TRAP OR TRAPPED FIXTURE BEING VENTED.
 SECTION 905.4. - STILL SHOWN ON THE
 FLOOR PLAN AND THE RISER DIAGRAM ARE
 HORIZONTAL DRY VENTS BELOW THE FLOOD
 LEVEL RIM OF THE W/C'S, TUBS, SHOWERS.
 THE PLANS SHALL REFLECT THE INSTALLATION
 OF THE PLUMBING. PLEASE SUBMIT A
 PLUMBING FLOOR PLAN AND SANT. RISER
 DIAGRAM THAT MEET THE CODE REQUIREMENT.
 SECTION 104.2.1.
 2) RESPONSE TO COMMENT #2 STATES "THERE
 IS CURRENTLY NO GAS SERVICE TO THE
 HOUSE". COMMENT 2D STATES "GAS LOAD
 EXISTING=130,000 BTU" PLEASE CLARIFY.
 SHOW EXISTING GAS CONNECTION TO THE
 PIPING OFF THE METER. PLEASE CLARIFY
 SECTION 104.2.1.
 3) BY NOT SHOWING THE DISTANCE FROM THE
 METER TO THE JACUZZI, WHEN THAT PIPE IS
 ADDED TO THE SYSTEM, THE PIPING FROM THE
 METER WILL HAVE TO BE CHANGED TO ACCOUNT
 FOR THE TOTAL DEVELOPED LENGTH OF THE
 SYSTEM. IF THIS IS SHOWN ON THE RISER
 DIAGRAM THE PIPE CAN BE SIZED FOR FUTURE
 APPLIANCES WHEN INSTALLED AT THIS TIME.
 TABLE 402(2).
 4) SUBMIT TWO SETS OF PLANS FOR REVIEW.
 REMOVE ALL VOIDED SHEETS AND RESUBMIT
 ONE SET FOR COMPAIRISON. SECTION
 104.2.1
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]