| 2004-11-05 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT P3 SANITARY RISER DIAGRAM, EVERY |
| | DRY VENT SHALL RISE VERTICALLY TO A |
| | MINIMUM OF 6 INCHES ABOVE THE FLOOD |
| | LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED |
| | FIXTURE BEING VENTED. SECTION 905.4 |
| | 2) THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR THE GAS PERMIT: |
| | A) SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS. |
| | B) SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF THE CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING |
| | USED) |
| | C) TYPE OF GAS, (NATURAL OR LP) |
| | D) BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS SECS. 401.8 THRU |
| | 402.5.2 AND TABLES 402(1) THRU 402(34) |
| | E) SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY< (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE FBC-2001 FUEL GAS APPENDIX A-USE OF |
| | CAPACITY TABLES(A)(3) |
| | F) SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER THE FBC-2001 FUEL GAS CODE SEC. |
| | 304 |
| | G) INDICATE THE DELIVERY PRESSURE(PSI) |
| | PER FBC-2001 FUEL GAS SEC 402.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI |
| | 3) PME SHEETS: THE DATE THAT THE |
| | SIGNATURE AND SEAL IS AFFIXED SHALL BE |
| | ENTERED ON PLANS. FAC 61G15-23.002(1) |
| | IF PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME, AND LICENSE |
| | NUMBER, AS WELL AS, THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS ON EACH |
| | SHEET. 61G15-23.002(2) FS 471.025 |
| | 4) RECORDS FROM DBPR STATE OF FLORIDA |
| | INDICATES THAT THELICENSE OF JACK A. |
| | GREEN IS DELINQUENT AT THIS TIME. THIS |
| | SHALL BE ACTIVATED PRIOR TO APPROVAL OF |
| | THE PLANS. (SEE ATTACHED SHEET) |
| | 5) ARCHITECTURAL SHEETS: THE PERSONAL |
| | SEAL, SIGNATURE AND DATE OF THE |
| | ARCHITECT SHALL APPEAR ON ALL |
| | ARCHITECTURAL DOCUMENTS TO BE FILED FOR |
| | PUBLIC RECORD. 61G1-16.003 AND LICENSE |
| | NUMBER SHALL APPEAR ON EACH SHEET. FS |
| | 481.219 |
| | |
| | |