 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS IMPOSED,ALL
 EXISTING LOADS AND THE EXISTING OR
 PROPOSED SERVICE SPECIFICATIONS PER
 215.15.
  
 2} NOTE THAT A SMALL APPLIANCE CIRCUIT
 REQUIRED BY 210.11(C)(1) IS MISSING
 FROM THE PANEL SCHEDULE.
  
 3} VERIFY THAT THE SYSTEM VOLTAGE IS
 208 AS THAT IS NOT COMMON VOLTAGE FOR A
 RESIDENTIAL AREA.
  
 4} THE DRYER CIRCUIT IS LISTED AS
 1-POLE 20 AMP, PLEASE VERIFY.
  
 5} CIRCUIT #26 ON THE PANEL SCHEDULE IS
 LISTED AS GENERAL CONVENIENCE. THIS
 CIRCUIT MUST COMPLY WITH 210.52(B) AND
 BE A SMALL APPLIANCE CIRCUIT.
  
 6} RECEPTACLE SPACING MUST COMPLY WITH
 210.52, SEE WALLS IN THE DINING ROOM
 ANDNEW WALLS IN THE LIVING ROOM.
  
 7} THE GUEST BATH REQUIRES ANOTHER
 RECEPTACLE TO COMPLY WITH THE 3'
 REQUIREMENT OF 210.52(D).
  
 8} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH 905.2.2 FBC., AND 8-1.4.1.6.
 2 NFPA-72. ALSO SEE 210.12.
  
 9} THE ENGINEERS TITLE BLOCK MUST
 CONTAIN A CERTIFICATE OF AUTHORIZATION
 NUMBER PER 61G15-23.002.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026