| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE PROVIDE A CALCULATION |
| | INCLUDING ALL ADDED LOADS IMPOSED,ALL |
| | EXISTING LOADS AND THE EXISTING OR |
| | PROPOSED SERVICE SPECIFICATIONS PER |
| | 215.15. |
| | |
| | 2} NOTE THAT A SMALL APPLIANCE CIRCUIT |
| | REQUIRED BY 210.11(C)(1) IS MISSING |
| | FROM THE PANEL SCHEDULE. |
| | |
| | 3} VERIFY THAT THE SYSTEM VOLTAGE IS |
| | 208 AS THAT IS NOT COMMON VOLTAGE FOR A |
| | RESIDENTIAL AREA. |
| | |
| | 4} THE DRYER CIRCUIT IS LISTED AS |
| | 1-POLE 20 AMP, PLEASE VERIFY. |
| | |
| | 5} CIRCUIT #26 ON THE PANEL SCHEDULE IS |
| | LISTED AS GENERAL CONVENIENCE. THIS |
| | CIRCUIT MUST COMPLY WITH 210.52(B) AND |
| | BE A SMALL APPLIANCE CIRCUIT. |
| | |
| | 6} RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52, SEE WALLS IN THE DINING ROOM |
| | ANDNEW WALLS IN THE LIVING ROOM. |
| | |
| | 7} THE GUEST BATH REQUIRES ANOTHER |
| | RECEPTACLE TO COMPLY WITH THE 3' |
| | REQUIREMENT OF 210.52(D). |
| | |
| | 8} SMOKE DETECTORS MUST BE INSTALLED TO |
| | COMPLY WITH 905.2.2 FBC., AND 8-1.4.1.6. |
| | 2 NFPA-72. ALSO SEE 210.12. |
| | |
| | 9} THE ENGINEERS TITLE BLOCK MUST |
| | CONTAIN A CERTIFICATE OF AUTHORIZATION |
| | NUMBER PER 61G15-23.002. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |